2. The following pressure vessels are excluded from the Act and its regulations:(1) steam, hot water or thermal fluid low-pressure boilers whose wet heating surface in less than 2.8 m2 or whose power does not exceed 30 kW;
(1.1) open-circuit boilers not mentioned in paragraph 1 whose pressure cannot exceed 103 kPa and which have no valve between the boiler and the vent leading directly to the atmosphere;
(1.2) hot water or steam boilers not mentioned in paragraphs 1 and 1.1 having all the following characteristics;(a) they have no steam drum or steam header;
(b) the tubes and coils are not used to produce steam;
(c) they are provided with manually operated nozzles or sprinklers that conduct the fluid directly into the atmosphere;
(d) the tubes have an outside diameter not exceeding 25 mm and the pipes have a nominal diameter not exceeding 19 mm;
(e) their water volume does not exceed 23 litres;
(f) they are provided with a temperature control device that prevents the water temperature from exceeding 180 ºC;
(g) they are provided with an overpressure safety relief device adjusted to and sealed at a pressure not exceeding the design pressure indicated on the boiler;
(2) water heaters whose power does not exceed 30 kW or whose diameter does not exceed 600 mm;
(3) hot water tanks not exceeding 600 mm in diameter and hot water tanks not provided with a power source and containing water at a temperature of 65 °C or less;
(4) pressure vessels other than those mentioned in subsection 3 not provided with a direct power source, containing vapour or a gas whose pressure cannot exceed 103 kPa or a liquid whose vapour pressure cannot exceed 205 kPa in absolute pressure at the maximum operating temperature. This exception does not apply to refrigerating systems;
(4.1) pressure vessels used as the enclosure for gas pressurized electric equipment and any tank forming a part thereof;
(5) hydropneumatic tanks with a diameter not exceeding 600 mm and with a volume not exceeding 0.453 m3;
(6) expansion tanks with a diameter not exceeding 600 mm;
(7) low-pressure piping and fire fighting piping;
(8) (paragraph revoked);
(9) (paragraph revoked);
(10) pressure vessels not provided with a direct power source with a volume not exceeding 0.0425 m3 or with a diameter not exceeding 152 mm.